Single Tank Inventory Control Panels
CPI-1H, 1D & 1N FOR ONE TANK
DESCRIPTION
Fluid Electronics, Inc. supplies a family of Inventory Control Panels designed for Single Tank installations - CPI 1. The panels are available in three models; CPI 1H; 1D; and 1N. All models provide monitoring for one inventory probe which includes intank water detection and several leak detection sensors, high and low fuel alarms, liquid detection in piping sumps and one of three leak detection capabilities in the annular space of double wall tanks. The CPI 1H provides leak detection via a dual float sensor in a "Hydrostatic" reservoir filled with Brine. The CPI 1D model provides "Discriminating" leak detection of the dry annular space, while the CPI 1N provides "Non-discriminating" leak detection of the dry annular space.
All panels are programmed at the factory in order to eliminate on-site programming requirements. The panels provide audible and visual readouts and optional printed reports for status of the various inventory probes and leak sensors. The CPI 1 panels provide a daylight visible display mounted on the exterior of the panel door. The standard panel enclosure is NEMA 1, a NEMA 4 enclosure is available as an option. The printer is not available with the NEMA 4 option. The CPI 1 panels are designed to work with Fluid Electronics' inventory probes (IPFW or IPFO), float switches (F series sensors) and liquid discriminating sensors (D series sensors) for intrinsically safe operation. See below for specific configurations.
SPECIFICATIONS
| Power Requirements |
120 VAC (± 10%, 60 Hz, 48 Watts) |
| Fuse |
3 AG SLO-BLO, 1/4 Amp, 250 VAC |
| Operating Temp |
-40°F to 122°F (-40°C to 50°C) |
| Enclosure Rating |
NEMA 1 Standard, NEMA 4 Optional |
| Installation |
Wall Mount |
| Calibrations |
Alarm points and programming set by keypad and maintained for 10 year data retention on power failure |
| Keypad |
Integral 16 key keypad for programming |
| Display |
Red, 0.8" high, seven segments |
| Alarm Indicators |
Red LED's |
| Horn |
Minimum 85 dB at 3 meters axis, reset button silences horn |
| Clock |
Maintains time and date |
| Relay Output |
4 SPDT Dry relay contacts rated 5 AMPS at 120 VAC; keypad programmable |
| Output Signals |
RS 232
Optional 4 to 20 mA: Non-isolated output, 500 ohms max. |
| Inventory Probe |
(1) from any IPFW or IPFO series probe; with any CPI Model. Intrinsically Safe for Class I, Div. 1, Groups A, B, C, D ;5 VDC at 45mA. |
| Probe Resolution |
0.1% of tank height |
| Probe Accuracy |
± 0.12% of tank height |
| Probe Repeatability |
± 0.1% of tank height |
| Float Switch |
Up to (3) from any F series float switch, with CPI 1H & N Models; Intrinsically Safe for Class I, Div. 1, Groups A, B, C, D; 5 VDC at 25mA. |
| Discriminating Sensor |
(1) DDAS 910 or DCBS 900 sensor, with CPI 1D Model only; Intrinsically Safe for Class I, Div. 1, Groups A, B, C, D; 5 VDC at 45mA. |
Note: Leak detection using the DDAS or DCBS sensors meets EPA requirements for annual testing and monthly monitoring
|
| Sensor Location |
Discriminating sensors up to 1000. Switch sensors up to 5000. Inventory probe to 5000. |
Printer Option
20 column dot matrix |
Product level & volume - on-demand
Set up parameters - on-demand
Alarms - automatic printout |
For further information on Electronic Monitoring Equipment, navigate to any of the areas below.
Electronics Section Navigation:
Control Panels
Sensors
Alarms
|
|