| Overfill Sensors
FOVF 600 Brass and Stainless Steel
DESCRIPTION
The FOVF 600 is a"Single Point" float switch sensor designed to provide a signal indicating that a liquid has reached a critical level. This sensor is used in conjunction with a control panel as a Tank Overfill Alarm System.
If installed in a 4" tank opening this sensor may be installed using a 4" x 2" reducing bushing for rigid mounting or it may be installed using an optional extractor fitting installation which allows easy removal of the sensor for inspection and maintenance.
SPECIFICATIONS
| Float Type |
1.6" Diameter, Stainless Steel |
| Float Stem |
1/2" Diameter Brass, (Stainless Steel Optional) |
| Connector Cable |
2 conductor - 18 AWG 10' length, PVC coated |
| Sensor Type |
Dry Reed Switch (Normally Closed) |
| Alarm Set Point |
1/8" from lower Retainer Clip |
| Temperature Range |
-20° to 180°F (-29° to 82°C) |
| Pressure |
Full Vacuum to 150 PSI |
| Switch Rating |
400 Watts, 3 AMPS at 120V (max.) |
| Installation Distance |
Up to 5000' from Fluid Electronics Control Panels |
| Options Special |
Manual float lift lever (NCL) |
FHLS 300 Brass and Stainless Steel
DESCRIPTION
The FHLS 300 is a Dual Float High and Low Level Float Switch Sensor. This sensor is designed to provide a signal indicating that a liquid has reached one of two predetermined alarm points within a storage tank. The high and low level alarm points are determined at time of purchase and are not field adjustable.The sensor must be installed in a "Vertical" position within the storage tank. The FHLS 300 sensor is Factory Mutual (FM) approved as an intrinsically safe system when used with Fluid Electronics' Control Panels. Intrinsically safe for Class I, II and III, Division 1, Groups A, B, C, D, E, F & G when used with Fluid Electronics' CPF Panels.
If installed in a 4" tank opening this sensor may be installed using a 4" x 2" reducing bushing for rigid mounting or it may be installed using an optional extractor fitting installation which allows easy removal of the sensor for inspection and maintenance.
SPECIFICATIONS
| Float Type |
1.6" Diameter, Stainless Steel |
| Float Stem |
1/2" Diameter Brass, (Stainless Steel Optional) |
| Connector Cable |
2 conductor - 18 AWG, (Each Switch) 10' length, PVC coated |
| Maximum Rating |
400 Watts, 3 AMPS at 120 VAC (max) |
Model
FHLS 304
FHLS 306
FHLS 308
FHLS 310
FHLS 312
|
4' Diameter Tank
6' Diameter Tank
8' Diameter Tank
10' Diameter Tank
12' Diameter Tank
|
| Sensor Type |
Dry Reed Switches (Normally Closed) |
| Alarm Set Points |
1/8" from lower retainer clips |
| Temperature Range |
-20° to 180°F (-29° to 82°C) |
| Pressure |
Full Vacuum to 150 PSI |
| Installation Distance |
Up to 5000' from Fluid Electronics Control Panels |
For further information on Electronic Monitoring Equipment, navigate to any of the areas below.