Multiple Tank Inventory Control Panels
CPI 4 CONTROL-PANEL FOR-ONE-TO-FOUR-TANKS
DESCRIPTION
Containment Solutions provides an Inventory Control Panel designed for Multiple Tank installations - CPI 4. The panel continuously monitors the level of fuel in up to 4 tanks and detects leak conditions from up to 16 sensors. The sensors can all be "non-discriminating" float switches or a combination of up to 8 switches and up to 8 "discriminating" dielectric sensors. Panels are programmed at the factory in order to eliminate on-site programming requirements. The panels provide audible and visual readouts and optional printed reports for status of the various inventory probes and leak sensors. The standard panel enclosure is NEMA 1, a NEMA 4 enclosure is available as an option. The printer is not available with the NEMA 4 option. The CPI 4 panels are designed to interface with Fluid Electronics' inventory probes (IPFW or IPFO), float switches (F series) and liquid discriminating sensors (D series) for intrinsically safe operation.
SPECIFICATIONS
| Power Requirements |
120 VAC (± 10%, 60 Hz, 50 Watts) |
| Fuse |
3 AG SLO-BLO, 1/4 Amp, 250 VAC |
| Operating Temp |
-40°F to 122°F (-40°C to 50°C) |
| Enclosure Rating |
NEMA 1 Standard, NEMA 4 Optional |
| Installation |
Wall Mount |
| Calibrations |
Alarm points and programming set by keypad and maintained for 10 year data retention on power failure |
| Keypad |
Integral 16 key keypad for programming |
| Visual Display |
Red, 0.8" high, seven segments. Display mode, Tank/Sensor select, Theft mode and Data Recall |
| Alarm Indicators |
Red LED's |
| Horn |
Minimum 85 dB at 3 meters on axis, reset button silences alarm |
| Clock |
Maintains time and date |
| Relay Output |
8 SPDT Dry relay contacts rated 5 AMPS at 120 VAC; keypad programmable |
| Output Signal |
RS 232 |
| Inventory Probe |
Up to(4) from any IPFW or IPFO series probe. Intrinsically Safe for Class I, Div. 1, Groups A, B, C, D; 5 VDC at 45mA. |
| Probe Resolution |
0.1% of tank height |
| Probe Accuracy |
± 0.12% of tank height |
| Probe Repeatability |
± 0.1% of tank height |
| Float Switch |
Up to (16) from any F series float switch, or (8) when D Series sensors are used. Intrinsically Safe for Class I, Div. 1, Groups A, B, C, D; 5 VDC at 25mA. |
| Discriminating Sensor |
Up to (8) D Series sensors. Intrinsically Safe for Class I, Div. 1, Groups A, B, C, D; 5 VDC at 45mA. |
Note: Leak detection using the Discriminating Sensors meet EPA requirements for annual testing and monthly monitoring
|
| Sensor Location |
Discriminating sensors up to 1000. Switch sensors up to 2200. Inventory probe to 2200. |
Printer Option
20 column dot matrix |
Product level & volume - on-demand
Set up parameters - on-demand
Alarms & deliveries - automatic printout |
For further information on Electronic Monitoring Equipment, navigate to any of the areas below.
Electronics Section Navigation:
Control Panels
Sensors
Alarms
|
|